63 A MCCB with high interrupting capacity for line protection
It's a 3-pole unit built for line protection, meaning it's the primary overcurrent device guarding the feeder, not a motor circuit protector. Interrupting capacity hits 242 kA at 240 V and still carries 187 kA at 415 V and 440 V, dropping to 121 kA at 500 V and 3 kA at 690 V.
It'll drop into a DIN-rail or panel-mount enclosure without needing to re-layout the gland plate. The shunt trip lets you remote-trip from an E-stop or PLC output; the aux switches give status feedback for the SCADA or a panel lamp. Power loss is 5.4 W maximum, so it won't cook the neighboring components in a crowded enclosure.