Skip to main content
Siemens 3VA2063-6HN42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2063-6HN42-0AA0 MCCB, 63 A, 4-Pole, ETU35

MPN3VA2063-6HN42-0AA0
Active

Siemens SENTRON 3VA2063-6HN42-0AA0, Molded case circuit breaker, 4-pole, 63 A, ETU350, 242 kA at 240 V, line protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2063-6HN42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2063-6HN42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W

Protection & Trip Unit

3VA2063-6HN42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2063-6HN42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-6HN42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2063-6HN42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-6HN42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2063-6HN42-0AA0 is a 4-pole molded case circuit breaker rated for 63 A continuous current at 40 °C through 70 °C, meaning no derating is needed across the full panel ambient range. The ETU350 electronic trip unit provides line protection with adjustable overload and short-circuit settings. Interrupting capacity reaches 242 kA at 240 V, 187 kA at 415/440 V, and 121 kA at 500 V — enough to clear high-fault conditions without cascading upstream breakers. Insulation voltage is rated at 800 V, with a maximum operating temperature of 70 °C and storage from -40 °C to 80 °C.

Dimensions are 86 mm deep, 140 mm wide, 181 mm high. The 4-pole form factor fits standard panel layouts; front IP40 protection keeps debris out of the breaker face in enclosed panels. No undervoltage release, no communication function, no ground-fault monitoring — this is a straight line-protection breaker with the ETU350 trip unit. Power loss is 5.4 W maximum at rated current.

No trip indicator is fitted, so fault events won't be visually flagged on the breaker itself — plan for remote indication via auxiliary contacts if needed. The 63 A rating holds steady across the full 40–70 °C range, which simplifies coordination in dense panels where ambient can climb.

Frequently asked questions

What are the key ratings for this breaker?

63 A continuous current (no derating from 40 °C to 70 °C), 4 poles, ETU350 electronic trip unit, interrupting capacity of 242 kA at 240 V, 187 kA at 415/440 V, 121 kA at 500 V, and 3 kA at 690 V. Insulation voltage is 800 V.

Where can I buy the 3VA2063-6HN42-0AA0?

This part is sourced to order against an RFQ through independent distribution. Current pricing and availability are confirmed at quote time — submit an RFQ for the latest commercial terms.

What is the physical size of this breaker?

86 mm deep, 140 mm wide, 181 mm high. Front IP40 protection. Fits standard 4-pole MCCB panel cutouts.

Does this breaker have a trip indicator or undervoltage release?

No trip indicator, no undervoltage release, no communication function, no ground-fault monitoring. It is a basic line-protection breaker with the ETU350 trip unit.

MPN
3VA2063-6HN42-0AA0