Skip to main content
Siemens 3VA2063-6KP42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2063-6KP42-0AA0 MCCB, 63 A, 4-Pole, ETU85

MPN3VA2063-6KP42-0AA0
Active

Siemens SENTRON 3VA series molded case circuit breaker, 3VA2063-6KP42-0AA0, 63 A, 4-pole, ETU850 electronic trip unit, line protection design, 242 kA breaking capacity at 240 V, IP40 front protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2063-6KP42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2063-6KP42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W
3VA2063-6KP42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2063-6KP42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2063-6KP42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2063-6KP42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2063-6KP42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

Breaking capacity is the headline here: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. The ETU850 trip unit gives you adjustable long-time, short-time, instantaneous, and ground-fault protection curves. Communication function is built in, so it can talk to a higher-level control system for monitoring and remote trip — useful for coordinated power management in a plant.

Termination is for copper or aluminum conductors up to the rated ampacity. No undervoltage release or shunt trip is included as standard — those are optional accessories if you need remote tripping beyond the communication function.

Frequently asked questions

What trip unit does this breaker use?

It uses the ETU850 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves. Communication function is built in for remote monitoring and control.

MPN
3VA2063-6KP42-0AA0