Skip to main content
Siemens 3VA2063-7HL36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-7HL36-0AA0 SENTRON MCCB, 63 A, 3-Pole, ETU32

MPN3VA2063-7HL36-0AA0
Active

Siemens SENTRON 3VA2063-7HL36-0AA0, molded case circuit breaker, 3-pole, 63 A, ETU320 electronic trip unit, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2063-7HL36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2063-7HL36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3 kA
Power loss, max.3 W
3VA2063-7HL36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2063-7HL36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2063-7HL36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2063-7HL36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2063-7HL36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The interrupting capacity hits 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3 kA at 690 V — so it handles high-fault utility feeds and transformer secondaries without cascading upstream.

The ETU320 electronic trip gives adjustable overload and short-circuit protection, which matters when coordinating with downstream feeders or motor starters.

Integration notes

Mounts in a standard MCCB cutout on a panel or switchboard. If you need those functions, this isn't the build; if you just need a reliable 63 A main or feeder with high interrupt capacity, it's a clean fit.

Frequently asked questions

Where can I buy 3VA2063-7HL36-0AA0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — submit an inquiry for your quantity and delivery window.

What is the interrupting capacity of this MCCB at different voltages?

330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3 kA at 690 V. These are the symmetrical ratings for line protection duty.

Does this breaker have a ground-fault or undervoltage release?

No. This variant is without ground-fault monitoring and without undervoltage release. It's a straight line-protection breaker with the ETU320 electronic trip.

MPN
3VA2063-7HL36-0AA0