Skip to main content
Siemens 3VA2063-7JP46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-7JP46-0AA0 SENTRON MCCB, 63 A, 4-Pole, ETU55

MPN3VA2063-7JP46-0AA0
Active

Siemens SENTRON 3VA2 series, molded case circuit breaker (MCCB), 3VA2063-7JP46-0AA0, 63 A rated, 4-pole, ETU550 electronic trip unit, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2063-7JP46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2063-7JP46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3 kA
Power loss, max.3 W
3VA2063-7JP46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2063-7JP46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2063-7JP46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2063-7JP46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2063-7JP46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

MCCB with ETU550 — 63 A, 4-Pole, Line Protection

The Siemens 3VA2063-7JP46-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 63 A continuous current, with four poles and an ETU550 electronic trip unit. It is designed for line protection in distribution panels and switchboards, carrying a 330 kA interrupting capacity at 240 V and 242 kA at 415 V. The 63 A rating holds across the full ambient temperature range from 40 °C to 70 °C — no derating needed for elevated panel temperatures up to that ceiling. That simplifies panel layout when the breaker sits near other heat sources.

This MCCB delivers 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3 kA at 690 V. Rated insulation voltage is 800 V, and the maximum operating temperature is 70 °C with a minimum of -25 °C.

Dimensions are 181 mm height, 140 mm width, and 86 mm depth. The 86 mm depth is the key fit dimension for shallow enclosures — verify gland-plate clearance if back-panel wiring is tight. Front-side IP40 protection covers the operator interface. Trip indicator is not fitted.

Frequently asked questions

Where can I buy 3VA2063-7JP46-0AA0 and get a price?

This MCCB is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What is the closest functional alternative to 3VA2063-7JP46-0AA0?

The 3VA2063-8JQ42-0AA0 is a peer within the same SENTRON 3VA2 family, but it carries a different trip unit and accessory configuration. The 3VA2063-7JP46-0AA0 uses an ETU550 electronic trip unit; the 8JQ42 variant uses a different trip curve and may lack the communication function. Panel cutout dimensions are shared, so it drops into the same footprint, but the trip unit difference means coordination studies must be re-run before substitution.

What are the key ratings for 3VA2063-7JP46-0AA0?

Continuous current 63 A, 4-pole, ETU550 electronic trip unit. Interrupting capacity: 330 kA at 240 V, 242 kA at 415 V, 187 kA at 500 V, 3 kA at 690 V. Dimensions: 181 x 140 x 86 mm.

MPN
3VA2063-7JP46-0AA0