Skip to main content
Siemens 3VA2063-7JQ36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2063-7JQ36-0AA0 MCCB, 63 A, 330 kA at 240

MPN3VA2063-7JQ36-0AA0
Active

Siemens SENTRON molded case circuit breaker, 3VA2063-7JQ36-0AA0, 3-pole, 63 A, ETU560 electronic trip, 330 kA at 240 V, 242 kA at 415 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2063-7JQ36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2063-7JQ36-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3 kA
Power loss, max.3 W

Protection & Trip Unit

3VA2063-7JQ36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor

Construction & Connection

3VA2063-7JQ36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-7JQ36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2063-7JQ36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-7JQ36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

63 A MCCB with ETU560 — what the ratings mean for panel fit

The Siemens SENTRON 3VA2063-7JQ36-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel schedules in warm enclosures. The ETU560 electronic trip unit gives you adjustable long-time, short-time, instantaneous, and ground-fault protection curves, so this breaker handles both feeder and main switchboard duty without swapping trip packs. Breaking capacity is the headline number for fault coordination: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3 kA at 690 V. At 415 V — the common industrial distribution voltage — 242 kA means this breaker can be installed upstream of most downstream devices without a current-limiting fuse ahead of it, provided the available fault current at the panelboard doesn't exceed that figure. The 86 mm depth and 105 mm width let it drop into standard Siemens 3VA switchboard mountings and most common MCC bucket footprints. Front IP40 protection means it's suited for indoor panel installation where tools or fingers might contact the front face but not for washdown zones.

Panel integration and wiring notes

At 181 mm height, 105 mm width, and 86 mm depth, the breaker fits standard 3VA mounting plates and withdrawable cradle options. The 3-pole form factor with line and load lugs accepts copper or aluminum conductors per the terminal range in the full datasheet. Ground-fault monitoring is configured for summation current formation on the L-conductor — verify the neutral CT placement if using 4-wire systems. Rated insulation voltage is 800 V, so the breaker is rated for 690 V phase-to-phase systems with margin. Maximum power loss is 3 W — negligible for panel thermal calculations but worth noting if multiple breakers are ganged in a sealed enclosure without forced ventilation. The ETU560 trip unit supports communication function, enabling integration with energy management systems or remote monitoring via the SENTRON communication modules. No undervoltage release is fitted as standard, and no voltage trigger is present — these are optional accessories if needed for your safety circuit design.

Environmental and storage limits

Operating temperature range is -25 °C to 70 °C, with storage from -40 °C to 80 °C. The storage range exceeds the operating range — that limit governs handling and warehousing, not running conditions. The 63 A rating holds across the full operating band without derating, as shown in the spec table.

Frequently asked questions

Where can I buy 3VA2063-7JQ36-0AA0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time, not published here due to batch and regional variation.

What is the closest functional second-source to 3VA2063-7JQ36-0AA0?

The 3VA2063-8JQ42-0AA0 is a sibling in the same 3VA platform but carries a higher continuous current rating and a different trip unit. It will not drop into the same panel without verifying the trip curve coordination and conductor sizing — the frame size and mounting footprint are shared, but the protection settings differ.

What is the depth of 3VA2063-7JQ36-0AA0?

The depth is 86 mm (3.39 in), with a width of 105 mm (4.13 in) and height of 181 mm (7.13 in). These dimensions match the standard 3VA frame and fit common MCC bucket cutouts and switchboard mountings.

What compliance documentation does Siemens provide for 3VA2063-7JQ36-0AA0?

Siemens provides the standard SENTRON declaration of conformity covering IEC 60947-2, plus RoHS and REACH compliance statements. The product reference code per IEC 81346-2 is Q. Full documentation is available through the Siemens Industry Online Support portal.

MPN
3VA2063-7JQ36-0AA0