Breaking capacity by voltage level
The 3VA2063-7KP46-0AA0: This MCCB delivers 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3 kA at 690 V. That 330 kA figure at 240 V covers high-fault utility feeds and transformer secondaries. The steep drop to 3 kA at 690 V is typical for a 63 A frame — it's not a 690 V main breaker.
Panel fit and environment
Dimensions are 86 mm deep, 140 mm wide, 181 mm tall. Front IP40 — sealed against tools and wires over 1 mm, but not washdown. Operating range spans -40 °C to 70 °C; storage stretches to 80 °C. Maximum power loss is 5.4 W. Mounts in a standard distribution panel or MCC bucket; the 4-pole width at 140 mm is wider than a 3-pole unit, so check your busbar and enclosure fill factor before committing the BOM line.