Skip to main content
Siemens 3VA2063-7KQ42-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-7KQ42-0DA0 SENTRON MCCB, 63 A, 4-Pole, 330 k

MPN3VA2063-7KQ42-0DA0

Siemens SENTRON 3VA2063-7KQ42-0DA0, molded case circuit breaker, 4-pole, 63 A, line protection, interrupting 330 kA at 240 V, 242 kA at 415 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2063-7KQ42-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20637KQ420AA0
3VA2063-7KQ42-0DA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.5 W
3VA2063-7KQ42-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L + N conductor
Grounding protection functionYes
3VA2063-7KQ42-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2063-7KQ42-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2063-7KQ42-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2063-7KQ42-0DA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2063-7KQ42-0DA0 is a 4-pole molded case circuit breaker rated for line protection, with a full-scale current of 63 A that holds flat from 40 °C through 70 °C — no derating needed across the typical panel ambient range. The breaker includes an undervoltage release and a ground-fault monitoring function using summation current formation on L+N conductors, so it can serve as both a line protector and a personnel-safety device in a single enclosure.

Panel Fit & Integration — 4-Pole Footprint with Communication

A communication function is built in, so it can report status and trip events to a higher-level control system without an external add-on module. Maximum power loss is 5.5 W, which keeps internal panel temperature rise manageable even in a densely populated enclosure.

Ratings That Matter for Selectivity and Coordination

The adjustable thermal-magnetic trip range spans from a minimum of 95 A to a maximum of 756 A, with an initial value of 16 A — this lets the breaker coordinate with downstream feeders while maintaining full short-circuit protection. At 690 V the interrupting rating drops to 3 kA, so this breaker is best applied on 240–500 V systems where the high kA ratings are available; for 690 V applications a different frame or series would be needed.

Frequently asked questions

Does 3VA2063-7KQ42-0DA0 include an undervoltage release?

Yes, it is equipped with an undervoltage release as the auxiliary release type.

MPN