Skip to main content
Siemens 3VA2110-0KQ42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-0KQ42-0AA0 SENTRON MCCB, 100 A, 4-Pole, ETU8

MPN3VA2110-0KQ42-0AA0
Active

Siemens SENTRON 3VA2110-0KQ42-0AA0, molded case circuit breaker, 4-pole, 100 A continuous rating, ETU860 electronic trip unit, 440 kA breaking capacity at 415 V, IP40 front protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-0KQ42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2110-0KQ42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.7.7 W
3VA2110-0KQ42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L + N conductor
Grounding protection functionYes
3VA2110-0KQ42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-0KQ42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2110-0KQ42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-0KQ42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2110-0KQ42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 100 A continuous current, with a maximum frame rating of 1 200 A and an adjustable minimum of 150 A. The ETU860 electronic trip unit handles the overcurrent protection curve, and the N-conductor protection is adjustable from OFF through 20 % to 160 % of the rated value. Ground-fault monitoring uses summation current formation on L+N conductors.

That footprint fits a standard MCCB cutout in a distribution panelboard; the 4-pole width matches the common 140 mm envelope for this class. Front IP40 protection means it's fine for indoor panel mounting but not washdown environments.

Communication function is present, and the breaker includes an other measurement function.

Frequently asked questions

What trip unit does this breaker use?

It uses the ETU860 electronic overcurrent release, with adjustable N-conductor protection from OFF through 20 % to 160 % of the rated value.

Does 3VA2110-0KQ42-0AA0 drop into a panel designed for 3VA1110-5ED32-0AA0?

The 3VA2110 series uses the same 140 mm width and 181 mm height as the 3VA1110, so the cutout and mounting pattern are the same. The 86 mm depth is also identical. No rewiring of the bus bars should be needed, but verify the lug kit compatibility — the 3VA2110 frame is rated to 1 200 A versus the 3VA1110's lower maximum, so the line-side lugs may differ.

MPN
3VA2110-0KQ42-0AA0