Skip to main content
Siemens 3VA2110-5HL32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5HL32-0BH0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5HL32-0BH0

Siemens SENTRON 3VA2110-5HL32-0BH0, molded case circuit breaker, 3-pole, 100 A, line protection, interrupting capacity 187 kA at 240 V AC, with undervoltage release.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2110-5HL32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105HL320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2110-5HL32-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.12.5 W
3VA2110-5HL32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2110-5HL32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-5HL32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2110-5HL32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-5HL32-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2110-5HL32-0BH0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current, with a flat derating curve from 40 °C through 70 °C — no reduction needed across typical panel ambient temperatures. It is designed for line protection in distribution panels and motor control centers, carrying a maximum interrupting capacity of 187 kA at 240 V AC and 121 kA at 415/440 V, dropping to 75.6 kA at 500 V and 3.7 kA at 690 V.

The interrupting ratings tell you the maximum fault current the breaker can safely clear at each voltage level: at 240 V it handles 187 kA, which covers most North American industrial service-entrance faults; at 415/440 V it still clears 121 kA, enough for heavy European distribution. The 86 mm depth, 105 mm width, and 181 mm height (3.39 x 4.13 x 7.13 inches) place it in a compact footprint for a 100 A MCCB — it fits standard panelboard mounting patterns without requiring oversize gutters.

Built-in auxiliary and release options

Frequently asked questions

Where can I buy 3VA2110-5HL32-0BH0 and how do I get a price?

This part is sourced and quoted to order against an RFQ. Submit a request with your target quantity and delivery timeline; availability and current pricing are confirmed at quote time.

What is the interrupting capacity of 3VA2110-5HL32-0BH0 at different voltages?

At 240 V it interrupts 187 kA; at 415 V and 440 V, 121 kA; at 500 V, 75.6 kA; and at 690 V, 3.7 kA.

Does 3VA2110-5HL32-0BH0 include an undervoltage release?

Yes, it ships with an undervoltage release (UVR) plus 2 auxiliary switches and 1 trip alarm switch (HQ).

MPN
3VA2110-5HL32-0BH0