Skip to main content
Siemens 3VA2110-5HL36-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2110-5HL36-0AG0 MCCB, 100 A, 3-Pole, ETU3

MPN3VA2110-5HL36-0AG0

Siemens SENTRON 3VA series molded case circuit breaker, 3VA2110-5HL36-0AG0, 3-pole, 100 A rated continuous current, ETU320 electronic trip unit, line protection version.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5HL36-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2110-5HL36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11

Ratings

3VA2110-5HL36-0AG0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5HL36-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320

Construction & Connection

3VA2110-5HL36-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5HL36-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2110-5HL36-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5HL36-0AG0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

What this MCCB delivers in the panel

The Siemens SENTRON 3VA2110-5HL36-0AG0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, carrying the same 100 A rating through 50 °C before the thermal derating curve begins — at 55 °C it's 96.25 A, at 60 °C it's 92.5 A, and at 70 °C it's 85 A. That means for a panel sitting at 50 °C ambient (common in a crowded enclosure), you still get full 100 A without oversizing the frame. The interrupting ratings climb to 187 kA at 240 V and 121 kA at 415 V, so this breaker handles high-fault utility feeds and transformer secondaries without cascading upstream. The ETU320 electronic trip unit gives you adjustable long-time, short-time, and instantaneous protection — no thermal bimetal drift to account for on a warm day.

Sizing and integration into a DIN-rail enclosure

At 105 mm wide, 181 mm tall, and 86 mm deep, this 3VA frame fits standard Siemens panel cutouts and busbar risers. The IP40 front protection means it's fine for a clean indoor panel; it's not rated for washdown zones. The auxiliary contact configuration ships as 1 auxiliary switch plus 1 trip alarm switch (HP type) — that gives you one NO/NC for status feedback to the PLC and one dedicated alarm contact for the trip event, so you don't have to share or add a separate alarm module. Maximum power loss is 10 W, which is modest for a 100 A frame — keep that in mind for thermal calculations in a sealed enclosure.

Sourcing this for a BOM line

The 3VA2110-5HL36-0AG0 is specified into the BOM as a line-protection MCCB with the ETU320 release. It is sourced and quoted to order against an RFQ through independent distribution — availability and current pricing are confirmed at quote time. For a panel originally built around the 3VA1010-2ED36-0AC0, this 3VA2110 frame is a different physical size and trip unit generation; it will not drop into the same cutout without panel modification. The 3VA2110 is the larger frame for higher interrupting capacity and the electronic trip option.

Frequently asked questions

Where can I buy 3VA2110-5HL36-0AG0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

Will 3VA2110-5HL36-0AG0 drop into a panel specified around 3VA1010-2ED36-0AC0?

No. The 3VA2110 frame is physically larger (105 mm wide vs the 3VA1010's 70 mm frame) and uses a different trip unit generation. It will not fit the same cutout or busbar spacing without panel modification.

What are the key interrupting ratings for 3VA2110-5HL36-0AG0?

At 240 V it interrupts 187 kA; at 415 V and 440 V it interrupts 121 kA; at 500 V it interrupts 79 kA; and at 690 V it interrupts 4.25 kA. The 100 A continuous rating holds through 50 °C ambient.

What compliance documentation does Siemens provide for this MCCB?

The SENTRON 3VA series carries UL 489, IEC 60947-2, and CSA C22.2 No. 5 certifications. RoHS and REACH declarations are available from Siemens on request.

MPN
3VA2110-5HL36-0AG0