Its interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — the steep drop above 500 V means this breaker is sized for low-voltage main or feeder duty, not 690 V branch circuits. The thermal-magnetic trip unit adjusts between 150 A and 1 200 A, so the 100 A frame carries headroom for coordination studies.
Built-in undervoltage release and auxiliary switching
Two HQ auxiliary switches are also integrated, giving the panel builder a Form-C feedback signal for the PLC or status lamp without adding a separate accessory block.
Thermal performance across the panel ambient range
Power dissipation maxes at 12.5 W, which is modest for a 100 A frame and won't drive a ventilation redesign in a typical IP54 cabinet.