Skip to main content
Siemens 3VA2110-5HL36-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5HL36-0HC0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5HL36-0HC0

Siemens SENTRON 3VA2110-5HL36-0HC0, molded case circuit breaker, 3-pole, 100 A continuous, 187 kA interrupting at 240 V, line protection, with shunt trip and 2 auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5HL36-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105HL360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2110-5HL36-0HC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5HL36-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-5HL36-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5HL36-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2110-5HL36-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5HL36-0HC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens 3VA2110-5HL36-0HC0 is a SENTRON molded case circuit breaker (MCCB) rated for 100 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to that ceiling. Three poles, line-protection design, with a shunt trip (STL) and two HQ auxiliary switches built in. Interrupting capacity hits 187 kA at 240 V, 121 kA at 415 V / 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V, so it handles high-fault utility feeds and transformer secondaries without cascading upstream.

Panel fit and mounting

Footprint is 105 mm wide, 181 mm tall, 86 mm deep — standard for a 3-pole 100 A frame in the 3VA2 family. Mounts on a DIN rail or directly to a backplate; the 86 mm depth leaves clearance behind a 200 mm deep enclosure gland plate. Shunt trip and auxiliary switches are factory-integrated, so no add-on modules eat extra DIN space.

Frequently asked questions

Where can I buy 3VA2110-5HL36-0HC0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of 3VA2110-5HL36-0HC0?

Continuous current 100 A, 3-pole, interrupting capacity 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, 3.7 kA at 690 V. Includes a shunt trip and two HQ auxiliary switches.

What is the depth of 3VA2110-5HL36-0HC0?

Depth is 86 mm (3.39 in).

What is the width of 3VA2110-5HL36-0HC0?

Width is 105 mm (4.13 in).

MPN