Skip to main content
Siemens 3VA2110-5HL36-0KL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5HL36-0KL0 SENTRON MCCB, 100 A, 150–1200 A t

MPN3VA2110-5HL36-0KL0

Siemens SENTRON 3VA2110-5HL36-0KL0, molded case circuit breaker, 3-pole, 100 A continuous, trip range 150–1200 A, interrupting capacity 187 kA at 240 V, 121 kA at 415/440 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5HL36-0KL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105HL360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2110-5HL36-0KL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5HL36-0KL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-5HL36-0KL0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5HL36-0KL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2110-5HL36-0KL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5HL36-0KL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB carries and where it fits

The Siemens SENTRON 3VA2110-5HL36-0KL0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full -25 °C to 70 °C operating range — no derating needed up to 70 °C ambient. Its electronic trip unit adjusts between 150 A and 1200 A, covering line-feeder and distribution protection in industrial panels. Interrupting capacity is voltage-dependent: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. That 187 kA figure at 240 V gives substantial headroom for high-fault panels — useful where the available fault current approaches 200 kA.

Physical integration and auxiliary configuration

Dimensions are 105 mm wide, 181 mm tall, and 86 mm deep — a standard 3-pole MCCB footprint for panel-mounting on a backplate or DIN rail adapter. The supplied basic switch is order code 3VA21105HL360AA0. Factory-fitted auxiliaries include 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type), plus a shunt trip (STL) release. The trip indicator and voltage trigger are present; undervoltage release and ground-fault monitoring are not fitted. Maximum power loss is 10 W.

What the interrupting ratings mean for selectivity

The 121 kA rating at 415 V and 440 V covers most European and Asian industrial distribution panels. At 690 V the rating drops to 3.7 kA — this breaker is not intended for primary 690 V feeders with high fault current; it is a line-protection device for standard low-voltage networks.

Frequently asked questions

What is the closest functional second-source for 3VA2110-5HL36-0KL0?

The peer order codes 3VA1110-5EF32-0AM0 and 3VA1110-5ED36-0AA0 are in the same SENTRON family but carry different trip-unit configurations and auxiliary layouts. The 3VA2110-5HL36-0KL0 is the line-protection variant with the full auxiliary switch set (2 aux + trip alarm + electrical alarm) and shunt trip — verify the specific trip range and aux count before substituting.

Will 3VA2110-5HL36-0KL0 drop into a panel specified around 3VA1110-5EF32-0AM0?

Both are 3-pole SENTRON MCCBs with the same basic frame dimensions, so the physical footprint is compatible. However, the auxiliary switch configuration and trip unit differ — the 3VA2110-5HL36-0KL0 carries 2 aux switches plus trip and electrical alarm switches, plus a shunt trip, which may require different wiring or panel layout. Verify the aux contact count and release type against your panel schematic before drop-in replacement.

MPN