The Siemens SENTRON 3VA2110-5HM42-0AA0 is a 4-pole molded case circuit breaker rated for 100 A continuous current with an adjustable thermal-magnetic trip unit covering 150 A to 1 200 A.
SCCR and selectivity
The interrupting ratings drop as voltage rises: 121 kA at 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. That steep curve at 690 V means this breaker is best applied on 400 V-class systems where its SCCR is highest.
Thermal performance and ground-fault
The ground-fault monitoring uses summation current sensing on L + N, so it picks up leakage on the protected circuit without a separate sensor. Power loss maxes at 10 W, manageable in a crowded panel.