Skip to main content
Siemens 3VA2110-5HM46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5HM46-0AA0 SENTRON MCCB, 100 A, 4-Pole, 187

MPN3VA2110-5HM46-0AA0
Active

Siemens SENTRON 3VA2110-5HM46-0AA0, molded case circuit breaker, 4-pole, 100 A continuous rating, 187 kA breaking capacity at 240 VAC, line protection design with ground-fault monitoring.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5HM46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2110-5HM46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5HM46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU330
Overcurrent protection functionLIG
Ground-fault monitoringSummation current formation L + N conductor
Grounding protection functionYes

Construction & Connection

3VA2110-5HM46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5HM46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2110-5HM46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5HM46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

What this MCCB delivers for the panel

The Siemens SENTRON 3VA2110-5HM46-0AA0 is a 4-pole molded case circuit breaker rated for 100 A continuous current with zero derating all the way up to 70 °C — so it holds its full 100 A in a warm enclosure without needing to oversize the frame. Breaking capacity runs 187 kA at 240 VAC, 121 kA at 415/440 VAC, 75.6 kA at 500 VAC, and 3.7 kA at 690 VAC, which covers most industrial service-entrance and feeder applications. The 800 V rated insulation voltage means it's comfortable on 480/600 V systems with margin.

Ground-fault and protection design

This MCCB includes ground-fault monitoring via summation current formation on the L + N conductors — it measures the vector sum of line and neutral current to detect leakage to ground. The design is line protection, meaning it's set up for feeder and main breaker duty rather than motor or generator protection. No undervoltage release, no trip indicator, and no communication function on this variant — it's a straightforward thermal-magnetic or electronic trip unit (trip type not specified in the listing) for hardwired distribution panels.

Panel fit and integration

Dimensions are 181 mm high, 140 mm wide, 86 mm deep — a standard MCCB footprint that fits most DIN-rail or panel-mount enclosures without surprises. Power loss is 10 W maximum, so heat dissipation in a sealed cabinet is manageable. Operating temperature range is -25 °C to 70 °C; storage from -40 °C to 80 °C. The 4-pole format (3 phases + neutral) is common for North American 120/208 V or 277/480 V wye systems where the neutral needs overcurrent protection.

Frequently asked questions

Where can I buy 3VA2110-5HM46-0AA0 and how is it quoted?

We source and quote this part to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for your volume and delivery needs.

What is the breaking capacity of 3VA2110-5HM46-0AA0 at different voltages?

Breaking capacity is 187 kA at 240 VAC, 121 kA at 415 VAC and 440 VAC, 75.6 kA at 500 VAC, and 3.7 kA at 690 VAC. This covers most industrial service-entrance and feeder applications up to 600 V class.

Does 3VA2110-5HM46-0AA0 derate at high ambient temperatures?

No derating needed — it holds the full 100 A continuous rating from 40 °C through 70 °C ambient. That's useful for warm enclosures or high-density panels where other breakers would require a larger frame.

MPN