SENTRON 3VA2110-5HN32-0CH0 — 100 A MCCB with ETU350 Trip Unit
It carries a 187 kA interrupting capacity at 240 V, stepping down to 121 kA at 415/440 V, 79 kA at 500 V, and 4.25 kA at 690 V — the ratings that tell you whether this breaker holds the fault current at your transformer secondary or main distribution point. Thermal derating is published in 5 °C steps from 40 °C to 70 °C: the breaker carries its full 100 A up to 50 °C, then drops to 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C.
Dimensions & Panel Fit
Trip Unit & Auxiliary Wiring
Auxiliary contacts include 2 form-C auxiliary switches plus 1 trip-alarm switch (HQ version), and the integrated auxiliary trip (3VA9608-0BB24) is wired separately for remote shunt-trip or alarm signalling.