Skip to main content
Siemens 3VA2110-5HN32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5HN32-0KC0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5HN32-0KC0

Siemens SENTRON 3VA2110-5HN32-0KC0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 187 kA interrupting capacity at 240 V AC, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5HN32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105HN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2110-5HN32-0KC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5HN32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-5HN32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5HN32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2110-5HN32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5HN32-0KC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2110-5HN32-0KC0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It's designed for line protection in distribution panels, switchboards, and motor control centers where you need a compact 105 mm wide footprint and a high interrupting capacity.

Interrupting capacity and selectivity

At 240 V this breaker clears 187 kA — that's the kind of number you need for high-fault utility feeds or transformer secondaries. At 415 V it still holds 121 kA, dropping to 75.6 kA at 500 V and 3.7 kA at 690 V. The 100 A frame with those interrupting ratings gives you solid selectivity headroom downstream; you can coordinate with smaller branch breakers without oversizing the main.

Built-in accessories and release options

This variant ships with two auxiliary switches (HQ type) and a shunt trip release (STL) factory-installed — no field retrofit needed. The shunt trip lets you remotely trip the breaker from an emergency stop or a protection relay, which saves panel space versus adding an external undervoltage release. Power loss is 10 W maximum, so thermal management inside a sealed enclosure is manageable.

Dimensions and panel fit

The breaker measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard SENTRON 3VA frame that fits most DIN-rail or panel-mount enclosures without surprises. The 86 mm depth is shallow enough for shallow backpanels; just verify the gland plate clearance if you're running cables behind the breaker.

Frequently asked questions

What is the interrupting capacity of 3VA2110-5HN32-0KC0 at 240 V?

At 240 V it clears 187 kA, dropping to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V.

What accessories come installed on this MCCB?

It includes two auxiliary switches (HQ type) and a shunt trip release (STL) factory-installed.

Where can I buy 3VA2110-5HN32-0KC0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

MPN
3VA2110-5HN32-0KC0