Skip to main content
Siemens 3VA2110-5HN36-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5HN36-0HA0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5HN36-0HA0

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2110-5HN36-0HA0, 100 A rated continuous current, 3-pole, line protection design with integrated shunt trip (STL), 187 kA breaking capacity at 240 VAC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5HN36-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105HN360AA0

Ratings

3VA2110-5HN36-0HA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5HN36-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-5HN36-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5HN36-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2110-5HN36-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5HN36-0HA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens 3VA2110-5HN36-0HA0 is a SENTRON 3VA2 molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C through 70 °C ambient, meaning no derating across the typical panel temperature range. It is a 3-pole device designed for line protection, with an integrated shunt trip (STL) auxiliary release for remote tripping.

Breaking capacity and fault clearance

This MCCB delivers 187 kA breaking capacity at 240 VAC, 121 kA at 415 VAC and 440 VAC, 75.6 kA at 500 VAC, and 3.7 kA at 690 VAC. The steep drop at 690 V means this breaker is sized for 480 V and below systems — at 690 V the interrupting rating falls to 3.7 kA, which is below most industrial fault-current levels at that voltage. For 690 V applications, a higher-rated 3VA2 variant would be needed.

Physical fit and panel integration

Dimensions are 181 mm height, 105 mm width, 86 mm depth. The 105 mm width is the standard 3-pole MCCB footprint for the 3VA2 frame — it occupies the same panel cutout as other 3VA2 3-pole units. The 86 mm depth includes the shunt trip projection; verify clearance to the enclosure door or deadfront.

Key ratings and design

Rated insulation voltage is 800 V. Maximum power loss is 10 W. The shunt trip (STL) allows remote tripping. The base switch is 3VA21105HN360AA0.

MPN
3VA2110-5HN36-0HA0