Skip to main content
Siemens 3VA2110-5HN36-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5HN36-0HC0 SENTRON MCCB, 100 A, 3-Pole, ETU3

MPN3VA2110-5HN36-0HC0

Siemens SENTRON 3VA2110-5HN36-0HC0, molded case circuit breaker, 3-pole, 100 A, ETU350 electronic trip unit, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-5HN36-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2110-5HN36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2110-5HN36-0HC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.10 W
3VA2110-5HN36-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2110-5HN36-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-5HN36-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2110-5HN36-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-5HN36-0HC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

What this MCCB delivers

The interrupting ratings climb with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. Thermal derating is published per degree: full 100 A up to 50 °C, then 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C.

Trip unit and auxiliary hardware

The integrated auxiliary trip module carries order code 3VA9688-0BL30; the basic switch assembly is 3VA2110-5HN36-0AA0. Both are field-replaceable without pulling the breaker from the panel.

Panel fit and environment

Maximum power loss is 10 W, so ventilation in a sealed enclosure is advisable if multiple breakers are ganged.

Frequently asked questions

How do I get current pricing and availability for 3VA2110-5HN36-0HC0?

Submit an RFQ through this listing. We source it to order through independent distribution and confirm availability and current pricing at quote time.

What is the interrupting rating of 3VA2110-5HN36-0HC0 at 240 V?

187 kA at 240 V, which is high for a 100 A frame — suitable for high-fault utility feeds without an upstream current-limiting device.

What trip unit does this breaker use?

It uses the ETU350 electronic trip unit with adjustable long-time, short-time, instantaneous, and ground-fault protection curves.

Does 3VA2110-5HN36-0HC0 include auxiliary contacts?

Yes, it ships with two HQ auxiliary switches for status feedback, plus a shunt trip release for remote tripping.

MPN
3VA2110-5HN36-0HC0