Skip to main content
Siemens 3VA2110-5HN36-0HL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5HN36-0HL0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5HN36-0HL0

Siemens SENTRON 3VA2110-5HN36-0HL0, molded case circuit breaker, 3-pole, 100 A continuous rating, 187 kA breaking capacity at 240 V AC, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5HN36-0HL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105HN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2110-5HN36-0HL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5HN36-0HL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-5HN36-0HL0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5HN36-0HL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2110-5HN36-0HL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5HN36-0HL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2110-5HN36-0HL0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Breaking capacity hits 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. That 187 kA figure at 240 V means it can interrupt a fault current nearly 190 times its rated load without welding or rupturing — critical for high-fault panels near large transformers or utility feeds.

Fit and integration

Footprint is 105 mm wide by 181 mm tall by 86 mm deep — a standard 3-pole MCCB envelope that fits Siemens SENTRON mounting plates and most DIN-rail adapter kits. The 10 W maximum power loss at full load is modest; no forced ventilation required in a typical IP54 enclosure, though keep it clear of heat-sensitive components above the breaker. Line protection design (no ground-fault monitoring, no communication module) keeps this a straightforward thermal-magnetic or electronic-trip MCCB — no auxiliary power wiring beyond the shunt trip (STL) if you order that option. The built-in trip indicator and voltage trigger give visual and electrical status for PLC or annunciator inputs.

Frequently asked questions

Where can I buy 3VA2110-5HN36-0HL0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate.

What is the breaking capacity of 3VA2110-5HN36-0HL0 at 240 V?

The breaking capacity is 187 kA at 240 V AC, which means it can safely interrupt a fault current up to 187,000 A at that voltage level.

MPN
3VA2110-5HN36-0HL0