Breaking capacity reaches 187 kA at 240 V AC and 121 kA at 415/440 V, dropping to 75.6 kA at 500 V and 3.7 kA at 690 V.
The 105 mm width (about 4.13 in) is the 3-pole frame; it occupies three 18 mm module spaces if you're thinking of DIN-rail layout. Shunt trip (STL) is built in, plus two auxiliary switches, one trip alarm switch, and one electrical alarm switch — all pre-configured from the factory. The 10 W max power loss is modest; no forced cooling needed in a ventilated enclosure.