Skip to main content
Siemens 3VA2110-5HN42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2110-5HN42-0AA0 MCCB, 100 A, 4-Pole, ETU3

MPN3VA2110-5HN42-0AA0
Active

Siemens SENTRON, molded case circuit breaker, 3VA2110-5HN42-0AA0, 100 A, 4-pole, ETU350 electronic trip unit, line protection, 121 kA at 415 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-5HN42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2110-5HN42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W
3VA2110-5HN42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2110-5HN42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-5HN42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2110-5HN42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-5HN42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

Breaking capacity and fit

At 415 V this MCCB interrupts 121 kA — that's the fault-clearing capacity for a 100 A frame, so it handles high available fault current on the secondary side of a typical 1 000 kVA transformer without cascading upstream. The 86 mm depth and 140 mm width match the standard SENTRON 3VA2 footprint, meaning it drops into the same panel cutout as the 3VA2116-5JP32-0AE0 (a 160 A frame) — same mounting pattern, same bus-bar spacing. You can swap the 100 A for the 160 A version later if the load grows, as long as the feeder and bus bars are sized for it.

Integration notes

The ETU350 trip unit is field-configurable — no need to pull the breaker for rating changes.

Environmental range

Rated for operation from -25 °C to 70 °C ambient, with no derating needed across that span — the 100 A rating holds at every temperature from 40 °C through 70 °C.

Frequently asked questions

How do I get pricing and availability for 3VA2110-5HN42-0AA0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the breaking capacity of this MCCB at 415 V?

121 kA at 415 V. This is the rated ultimate short-circuit breaking capacity (Icu) for the 100 A frame.

Will 3VA2110-5HN42-0AA0 fit in a panel designed for 3VA2116-5JP32-0AE0?

Yes, the 86 mm depth and 140 mm width are identical across the 3VA2 frame family. The 100 A and 160 A versions share the same mounting footprint and bus-bar spacing.

What trip unit does this breaker use?

An ETU350 electronic trip unit. It provides adjustable overload and short-circuit protection settings without requiring a breaker swap.

MPN
3VA2110-5HN42-0AA0