Siemens 3VA2110-5HN42-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5HN42-0KH0 Circuit Breaker, 55kA @ 415V, 100

MPN3VA2110-5HN42-0KH0

Siemens 3VA2 IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 4-pole, line protection ETU350, LSI, In=100A, overload protection Ir=40A...100A, short-circuit protection Isd=1.5...10 x Ir, Ii=12 x In, N conductor protection adjustable (OFF, 50%, 100%), nut keeper kit, Shunt trip left 208-277 V AC 50/60 Hz 220-250 V DC, accessory 2 Auxiliary switch changeover H, 1 Trip alarm switch changeover.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

What you're looking at

The Siemens 3VA2110-5HN42-0KH0 is a 4-pole IEC frame 160 molded-case circuit breaker with a 55 kA breaking capacity at 415 V — that's class M, meaning it handles moderate fault levels common in industrial distribution without needing a current-limiting upstream device. The ETU350 electronic trip unit gives you LSI protection (long-time, short-time, instantaneous) plus adjustable neutral protection (OFF, 50%, or 100% of phase setting). Rated In is 100 A, with overload Ir adjustable from 40 A to 100 A and short-time pickup Isd from 1.5 to 10 × Ir.

What the ratings mean for fit

The 55 kA Icu at 415 V is the ultimate breaking capacity — the breaker can safely interrupt a fault of that magnitude once and still be functional afterward. For most industrial panel applications, that's enough to coordinate with a downstream transformer or a 400 V motor control center without cascading. The ETU350's LSI curve lets you set short-time delay (Isd) to ride through motor inrush or downstream breaker coordination, then clear hard faults fast. The adjustable neutral is a nice touch for 3-phase + N panels where you need to protect the neutral conductor at a lower rating than the phase conductors — common in harmonic-rich loads like VFD banks or UPS inputs.

Panel integration notes

Mounts on a standard DIN rail or directly to a backplate via the frame's mounting holes. The nut keeper kit is included, which saves time when you're torqueing down lugs in a tight enclosure — no dropped hardware. The shunt trip wiring lands on the left-side terminals; keep the control circuit separate from the power conductors to avoid induced pickup on the trip signal. The auxiliary switch and trip alarm switch are pre-wired to a common terminal block on the front face, so you can land your PLC inputs without opening the breaker cover.

Frequently asked questions

Where can I buy the 3VA2110-5HN42-0KH0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm number.

What is the breaking capacity of this breaker?

The 3VA2110-5HN42-0KH0 has an Icu of 55 kA at 415 V AC, which is the class M breaking capacity for the 3VA2 frame.

What trip unit does the 3VA2110-5HN42-0KH0 use?

It uses the ETU350 electronic trip unit with LSI protection (long-time, short-time, instantaneous) and adjustable neutral protection (OFF, 50%, 100%).