Skip to main content
Siemens 3VA2110-5JP32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5JP32-0AA0 SENTRON MCCB, 100 A, 3-Pole, ETU5

MPN3VA2110-5JP32-0AA0
Active

Siemens SENTRON 3VA2110-5JP32-0AA0, molded case circuit breaker, 3-pole, 100 A rated continuous current, ETU550 electronic trip unit, 187 kA breaking capacity at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5JP32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2110-5JP32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5JP32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-5JP32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5JP32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2110-5JP32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5JP32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB is and what it carries

The Siemens 3VA2110-5JP32-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 100 A continuous current across its full ambient temperature range — from 40 °C through 70 °C, the 100 A rating holds without derating. That is unusual for an MCCB in this class and simplifies panel sizing when the breaker sits near other heat sources. It is a 3-pole unit fitted with the ETU550 electronic trip unit. The ETU550 provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves — a step up from thermal-magnetic trip units for selectivity coordination in distribution panels. Breaking capacity is rated at 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. The 690 V figure is low enough that this breaker is not a primary choice for 690 V line-side faults; it is sized for 400 V-class distribution where the interrupting duty is well within its margin.

Mounting and panel fit

Dimensions are 105 mm wide, 181 mm high, 86 mm deep. The 105 mm width is a standard 3-pole MCCB footprint on a DIN rail or bolted bus; verify the existing panel's bus-bar spacing and gland-plate clearance against the 86 mm depth before committing the BOM line. Front-face protection is IP40, meaning tools and fingers are kept out but the breaker is not sealed against water ingress — standard for indoor switchgear enclosures.

Communication and monitoring capability

This breaker includes a communication function — the ETU550 trip unit supports data exchange over the SENTRON communication bus (COM module required, sold separately). That allows remote reading of load current, trip event logging, and parameter adjustment from a panel-side HMI or a higher-level energy management system. Power loss is rated at 10 W maximum at rated current — negligible for panel thermal budgeting but worth noting if the enclosure is densely packed and ventilation is marginal.

Frequently asked questions

What is the closest functional second-source to 3VA2110-5JP32-0AA0?

The peer MPNs 5SQ2370-2YA05, 5SQ2370-2YA04, and 5SQ2370-2YA01 are functionally similar SENTRON MCCBs, but verify the trip unit type and breaking capacity ratings for your specific fault-current duty before substituting.

MPN
3VA2110-5JP32-0AA0