Skip to main content
Siemens 3VA2110-5JP32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2110-5JP32-0AF0 MCCB, 100 A, 187 kA IC

MPN3VA2110-5JP32-0AF0

Siemens SENTRON molded case circuit breaker, 3VA2110-5JP32-0AF0, 3-pole, 100 A rated current, ETU550 electronic trip unit, 187 kA interrupting capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-5JP32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2110-5JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2110-5JP32-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.10 W
3VA2110-5JP32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
3VA2110-5JP32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-5JP32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2110-5JP32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-5JP32-0AF0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

This is a line-protection version — no voltage trip, no phase-failure detection, no ground-fault monitoring module built in. Communication function is present, so it can talk to a higher-level system via the SENTRON bus.

Panel fit and thermal derating

Thermal derating is published: full 100 A up to 50 °C ambient, then it steps down to 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. If your panel hits 55 °C near the top of the enclosure, you lose about 4 A per pole — plan the load accordingly.

The interrupting capacity curve drops from 187 kA at 240 V to 121 kA at 415/440 V, then to 79 kA at 500 V, and 4.25 kA at 690 V. For 480 V distribution, the 79 kA at 500 V gives you headroom for most industrial services. The ETU550 allows zone-selective interlocking if paired with a compatible upstream breaker, which can reduce arc-flash incident energy on the line side.

MPN
3VA2110-5JP32-0AF0