Skip to main content
Siemens 3VA2110-5JP32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5JP32-0CC0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5JP32-0CC0

Siemens SENTRON 3VA series molded case circuit breaker, 3VA2110-5JP32-0CC0, 3-pole, 100 A continuous, 187 kA breaking capacity at 240 V AC, line protection design with undervoltage release and communication function.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-5JP32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105JP320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2110-5JP32-0CC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.12.5 W
3VA2110-5JP32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2110-5JP32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-5JP32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2110-5JP32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-5JP32-0CC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2110-5JP32-0CC0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to that ceiling. Breaking capacity sits at 187 kA at 240 V AC, dropping to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 3.7 kA at 690 V. This is a line-protection design (not feeder or motor-protection profile), so it's suited for main or branch circuits where the priority is short-circuit and overload isolation rather than motor thermal overload curves.

The 86 mm depth matters when the panel door clearance is tight; check that the handle and any rotary-drive extension clear the enclosure cover.

Frequently asked questions

Does 3VA2110-5JP32-0CC0 include an undervoltage release?

Yes, it includes an undervoltage release (UVR) as the auxiliary release type.

MPN
3VA2110-5JP32-0CC0