That 100 A holds steady at every temperature step the evidence lists, so you don't have to oversize for a hot enclosure. With three poles and a line-protection design, this MCCB is built for feeder and distribution circuits in commercial and industrial switchboards.
Breaking capacity — what it means at your voltage
Rated breaking capacity changes with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V.