Skip to main content
Siemens 3VA2110-5JP32-0DL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5JP32-0DL0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5JP32-0DL0

Siemens SENTRON 3VA2110-5JP32-0DL0, molded case circuit breaker, 3-pole, 100 A continuous, 187 kA at 240 V, line protection with undervoltage release and communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5JP32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105JP320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2110-5JP32-0DL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.12.5 W

Protection & Trip Unit

3VA2110-5JP32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-5JP32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5JP32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2110-5JP32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5JP32-0DL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Integrator note — 3VA2110-5JP32-0DL0

The Siemens SENTRON 3VA2110-5JP32-0DL0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Its interrupting capacity hits 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. That SCCR headroom makes it a fit for high-fault utility feeds or transformer secondaries where a standard MCCB would cascade. The breaker includes an undervoltage release and a communication function, plus a 2-auxiliary-switch + 1-trip-alarm + 1-electrical-alarm HQ auxiliary switch block. Panel space: 105 mm wide, 181 mm tall, 86 mm deep.

Selectivity & coordination

Rated for line protection, the 3VA2110-5JP32-0DL0 is designed for selectivity in distribution panels. The 100 A continuous rating and 187 kA SCCR at 240 V mean it can sit downstream of a larger main breaker and still clear a bolted fault without upstream trip — provided the upstream device's let-through is coordinated. The undervoltage release (UVR) allows remote shunt-trip for emergency-off circuits. Communication function supports integration with a BMS or PLC for load-shedding or power-quality monitoring.

Mounting & integration

Mounts on a standard DIN rail or panel-mount base. The auxiliary switch block (2 aux + 1 trip alarm + 1 electrical alarm HQ) occupies the left-side accessory slot. The UVR coils are wired to a separate control voltage — verify polarity and voltage rating before energizing. Power loss is 12.5 W maximum; account for that in enclosure thermal calculations, especially in a sealed panel above 50 °C.

Frequently asked questions

Where can I buy 3VA2110-5JP32-0DL0 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What is 3VA2110-5JP32-0DL0's interrupting capacity at 240 V?

187 kA at 240 V, which drops to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V.

What compliance documentation does this brand provide for 3VA2110-5JP32-0DL0?

As a Siemens SENTRON product, it carries the standard CE, UL, and CSA certifications for molded case circuit breakers. RoHS and REACH declarations are available through the manufacturer's documentation portal.

MPN
3VA2110-5JP32-0DL0