Skip to main content
Siemens 3VA2110-5JP32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2110-5JP32-0HA0 MCCB, 100 A, 187 kA at 24

MPN3VA2110-5JP32-0HA0

Siemens SENTRON molded case circuit breaker, 3VA2110-5JP32-0HA0, 3-pole, 100 A rated continuous current, line protection, ETU550 electronic trip unit, 187 kA breaking capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-5JP32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2110-5JP32-0AA0
3VA2110-5JP32-0HA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.10 W
3VA2110-5JP32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
3VA2110-5JP32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-5JP32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2110-5JP32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-5JP32-0HA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Siemens SENTRON 3VA2110-5JP32-0HA0 — 100 A MCCB with ETU550 Trip Unit

At 55 °C it derates to 96.25 A, at 60 °C to 92.5 A, at 65 °C to 88.75 A, and at 70 °C to 85 A.

Trip Unit and Auxiliaries

The ETU550 is an electronic trip unit with LSI protection curves. This variant ships without ground-fault monitoring and without an auxiliary contact block. It includes a communication function and a shunt trip (STL) for remote tripping. The base switch is order code 3VA2110-5JP32-0AA0, and the integrated auxiliary trip is 3VA9688-0BL30. If you need to order spare trip units or auxiliaries separately, those are the reference numbers.

Frequently asked questions

What trip unit does the 3VA2110-5JP32-0HA0 use?

It uses an ETU550 electronic trip unit with LSI protection curves. This variant ships without ground-fault monitoring and without auxiliary contacts.

MPN