Skip to main content
Siemens 3VA2110-5JP32-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5JP32-0KA0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5JP32-0KA0

Siemens SENTRON 3VA2110-5JP32-0KA0, molded case circuit breaker, 3-pole, 100 A continuous, 187 kA at 240 V, line protection with shunt trip.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5JP32-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105JP320AA0

Ratings

3VA2110-5JP32-0KA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5JP32-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-5JP32-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5JP32-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2110-5JP32-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5JP32-0KA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2110-5JP32-0KA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It is designed for line protection in distribution panels, with a shunt trip (STL) auxiliary release and communication function for integration into monitored systems.

Breaking capacity across voltage levels

This MCCB delivers 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. The steep drop at 690 V is typical for this frame size — the internal arc energy scales with voltage, and the 3.7 kA figure means it is not the right choice for high-fault 690 V feeders unless the available fault current is below that threshold.

Physical fit and panel integration

Dimensions are 105 mm wide, 181 mm high, and 86 mm deep. The 105 mm width is a standard 3-pole MCCB footprint.

Key ratings and what they mean for selection

The 100 A continuous rating is confirmed at every 5 °C increment from 40 °C to 70 °C — no thermal derating curve to apply in a warm enclosure. The insulation voltage is rated 800 V, which covers 480/277 V and 600 V systems with margin. The shunt trip (STL) allows remote tripping via a control signal; the communication function supports integration with building management or SCADA systems for status and alarm monitoring.

Frequently asked questions

What is 3VA2110-5JP32-0KA0's listed depth?

The depth is 86 mm (3.39 in), measured from the mounting surface to the furthest protrusion including the shunt trip and communication module.

MPN
3VA2110-5JP32-0KA0