Siemens 3VA2110-5JP36-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5JP36-0AF0 Circuit Breaker, 55kA @ 415V, 100

MPN3VA2110-5JP36-0AF0

Siemens 3VA2 IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 3-pole, ETU550 LSI, In=100A, overload Ir=40A…100A, short-circuit Isd=0.6…10x In, Ii=1.5…12x In, with 1 auxiliary switch changeover H and 1 trip alarm switch changeover.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

What this MCCB carries

The Siemens 3VA2110-5JP36-0AF0 is a 3-pole IEC frame 160 molded-case circuit breaker rated for line protection with an ETU550 electronic trip unit offering LSI (long-time, short-time, instantaneous) protection curves. Its headline breaking capacity is 55 kA at 415 V, placing it in breaking capacity class M — sufficient for high-fault-current industrial distribution panels where upstream transformer capacity drives available fault current above 25 kA. The continuous current rating In is 100 A, with overload protection Ir adjustable from 40 A to 100 A. Short-time pickup Isd spans 0.6 to 10 times In, and instantaneous pickup Ii ranges 1.5 to 12 times In. This range lets the breaker coordinate with downstream feeders and motor starters without nuisance tripping on inrush. Neutral conductor protection is optional via an external current transformer, supporting up to 160% of the phase rating. The breaker ships with one auxiliary switch (changeover H) and one trip alarm switch (changeover) — both factory-fitted, saving a panel-builder wiring step.

Lifecycle and sourcing

For BOM-line commitment, the key ratings to verify against your existing coordination study are the 55 kA interrupting capacity at 415 V and the adjustable LSI settings — these are the parameters that govern selectivity with upstream and downstream devices. Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

Frequently asked questions

What is the breaking capacity of this MCCB?

The interrupting rating Icu is 55 kA at 415 V, breaking capacity class M per IEC 60947-2.

What protection functions does the ETU550 trip unit provide?

The ETU550 provides LSI protection: long-time (overload) adjustable 40–100 A, short-time pickup 0.6–10x In, and instantaneous pickup 1.5–12x In.