Skip to main content
Siemens 3VA2110-5JQ32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5JQ32-0AB0 SENTRON MCCB, 100A Frame, 20A Con

MPN3VA2110-5JQ32-0AB0

Siemens SENTRON 3VA2110-5JQ32-0AB0, molded case circuit breaker, 3-pole, 100 A frame, 20 A continuous rating, line protection design, 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-5JQ32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105JQ320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11
3VA2110-5JQ32-0AB0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W
3VA2110-5JQ32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes
3VA2110-5JQ32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-5JQ32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2110-5JQ32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-5JQ32-0AB0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2110-5JQ32-0AB0 is a 3-pole molded case circuit breaker (MCCB) on a 100 A frame, set for 20 A continuous current at 40 °C through 70 °C — flat thermal derating across the full operating range. Line protection design means it's configured for feeder and branch-circuit overcurrent, not motor or generator protection. Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V and 440 V, then drops to 75.6 kA at 500 V and 3.7 kA at 690 V (–) — that 690 V figure tells you this frame is optimized for low-voltage distribution, not 690 V motor circuits where the fault current capability narrows sharply.

Panel footprint and integration

That 105 mm width on a 3-pole frame is tight for the breaking capacity it carries — expect standard DIN-rail or screw-mount panel integration. The unit includes 2 HP auxiliary switches factory-fitted; no undervoltage release fitted, no voltage trip. Communication function present — the basic switch variant is 3VA21105JQ320AA0, so the -0AB0 suffix adds the aux switch package and communication interface.

Frequently asked questions

What is 3VA2110-5JQ32-0AB0's listed depth?

The listed depth is 86 mm, with a width of 105 mm and height of 181 mm.

What compliance documentation does this brand provide for 3VA2110-5JQ32-0AB0?

As a Siemens SENTRON series MCCB, the part generally carries IEC/EN certifications for distribution-board use. RoHS/REACH declarations are standard for current-production Siemens industrial components. Verify the specific UL/CSA mark for your jurisdiction at quote time — the spec record does not list individual approvals.

MPN
3VA2110-5JQ32-0AB0