Skip to main content
Siemens 3VA2110-5JQ32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5JQ32-0JH0 SENTRON MCCB, 100 A, 150-1200 A T

MPN3VA2110-5JQ32-0JH0

Siemens SENTRON 3VA2110-5JQ32-0JH0, 3-pole molded case circuit breaker, 100 A continuous, adjustable thermal-magnetic trip 150-1200 A, interrupting 187 kA at 240 V, with shunt trip and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5JQ32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105JQ320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2110-5JQ32-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5JQ32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2110-5JQ32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5JQ32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2110-5JQ32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5JQ32-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Fitted accessories and communication

This variant ships with a shunt trip (STL) release and a complement of auxiliary switches: two auxiliary switches plus one trip alarm switch HQ. That covers remote tripping and status feedback without ordering separate add-on kits. A communication function is built in, which means it can talk to a higher-level controller or BMS for metering and status — no external module required on this order code.

Dimensions and panel fit

The case measures 86 mm deep, 105 mm wide, and 181 mm tall. That depth (86 mm) means it fits standard-depth panel enclosures without protruding past the gland plate, and the 105 mm width occupies three pole spaces on a DIN rail or mounting plate.

Frequently asked questions

Does 3VA2110-5JQ32-0JH0 include a shunt trip?

Yes, it ships with a shunt trip (STL) release plus two auxiliary switches and one trip alarm switch HQ.

MPN
3VA2110-5JQ32-0JH0