Skip to main content
Siemens 3VA2110-5JQ32-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5JQ32-0KH0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5JQ32-0KH0

Siemens SENTRON 3VA2110-5JQ32-0KH0, molded case circuit breaker, 3-pole, 100 A, 187 kA at 240 V, line protection, with communication function.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-5JQ32-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105JQ320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2110-5JQ32-0KH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W
3VA2110-5JQ32-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes
3VA2110-5JQ32-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-5JQ32-0KH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2110-5JQ32-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-5JQ32-0KH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens SENTRON 3VA2110-5JQ32-0KH0 — 100 A MCCB with 187 kA Interrupting Capacity

At 415 V and 440 V the rating holds at 121 kA, dropping to 75.6 kA at 500 V and 3.7 kA at 690 V, which covers the common low-voltage industrial range. That simplifies panel sizing: the breaker delivers its nameplate 100 A even when the cabinet is running hot. Physical footprint is 86 mm deep by 105 mm wide by 181 mm tall, a standard SENTRON 3VA form factor that fits the same panel cutouts and busbar risers as other 100 A frames in the series.

Maximum power loss is 10 W, which is modest for a 100 A frame and keeps internal cabinet heating manageable.

Frequently asked questions

Where can I buy 3VA2110-5JQ32-0KH0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the interrupting capacity of 3VA2110-5JQ32-0KH0 at different voltages?

187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V.

Does 3VA2110-5JQ32-0KH0 include auxiliary switches or a shunt trip?

Yes, it comes with 2 auxiliary switches plus 1 trip alarm switch (HQ) and a shunt trip release (STL).

MPN
3VA2110-5JQ32-0KH0