Skip to main content
Siemens 3VA2110-5JQ36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2110-5JQ36-0AA0 MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5JQ36-0AA0
Active

Siemens SENTRON 3VA2110-5JQ36-0AA0, molded case circuit breaker, 3-pole, 100 A continuous, interrupting 187 kA at 240 V, line protection with communication.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5JQ36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2110-5JQ36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5JQ36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2110-5JQ36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5JQ36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2110-5JQ36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5JQ36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What it is and what the ratings mean for fit

The Siemens SENTRON 3VA2110-5JQ36-0AA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current from 40 °C to 70 °C. Interrupting capacity is the headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. For a 100 A frame those numbers give serious SCCR headroom — it can sit upstream of a distribution board without worrying about cascading faults, as long as the available fault current at its terminals stays under those curves. Rated insulation voltage is 800 V, so it handles 690 V line-to-line with margin on the insulation coordination. The adjustable thermal-magnetic trip range runs from 150 A to 1 200 A — that's the magnetic pickup window, not the continuous rating. Set the magnetic threshold to coordinate with downstream branch breakers.

Mounting and integration

Footprint: 105 mm wide, 181 mm tall, 86 mm deep. That's a standard SENTRON 3VA fixed-panel mount — bolts onto the backplate, no DIN rail. The 86 mm depth means it clears a 200 mm deep enclosure with room for wiring gutters. This variant includes a communication function for a COM module slot, enabling status and trip reporting to a PLC or SCADA. No undervoltage release fitted. Power loss is 10 W maximum — negligible for panel thermal budgeting, but worth noting if you're packing multiple breakers in a sealed enclosure.

Frequently asked questions

Does this MCCB include communication capability?

Yes, the communication function is present on this variant. It accepts a COM module for fieldbus integration, allowing trip and status signals to be read by a PLC or SCADA system.

MPN
3VA2110-5JQ36-0AA0