MCCB for line protection with ETU850 trip unit
It carries a 187 kA breaking capacity at 240 V, dropping to 121 kA at 415 V and 440 V, and 79 kA at 500 V — enough for high-fault utility feeds or transformer secondaries.
The 100 A rating holds from 40 °C up to 50 °C, then derates to 96.25 A at 55 °C and 85 A at 70 °C — so in a warm enclosure you lose headroom above 50 °C.