Skip to main content
Siemens 3VA2110-5KP32-0CL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5KP32-0CL0 SENTRON MCCB, 100 A, 3-Pole, ETU8

MPN3VA2110-5KP32-0CL0

Siemens SENTRON 3VA2110-5KP32-0CL0, molded case circuit breaker, 3-pole, 100 A, ETU850 electronic trip unit, line protection, 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-5KP32-0CL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2110-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2110-5KP32-0CL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.12.5 W
3VA2110-5KP32-0CL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
3VA2110-5KP32-0CL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-5KP32-0CL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts4
3VA2110-5KP32-0CL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-5KP32-0CL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The 100 A rating holds flat from 40 °C to 50 °C, then derates to 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C — so if the panel ambient runs above 50 °C, the breaker's effective capacity drops; size the load accordingly. Its interrupting ratings are substantial: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. The ETU850 electronic trip gives adjustable curves and communication capability — this variant includes a communication function and an undervoltage release (UVR). No ground-fault monitoring or phase-failure detection on this unit.

Frequently asked questions

Will 3VA2110-5KP32-0CL0 drop into a panel that was specified around 3VA1112-5EF32-0CA0 without rewiring?

The 3VA2110-5KP32-0CL0 is a 3-pole 100 A MCCB with an ETU850 electronic trip, while the 3VA1112-5EF32-0CA0 is a different frame and rating. Panel fit depends on bus-bar spacing and cutout dimensions — verify the frame size matches your existing panel layout before swapping.

MPN
3VA2110-5KP32-0CL0