Siemens 3VA2110-5KP32-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5KP32-0DC0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5KP32-0DC0

Siemens SENTRON series, molded case circuit breaker (MCCB), 3VA2110-5KP32-0DC0, 3-pole, 100 A continuous, 187 kA interrupting at 240 V, line protection design with communication function and undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5KP32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105KP320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2110-5KP32-0DC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.12.5 W

Protection & Trip Unit

3VA2110-5KP32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-5KP32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5KP32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2110-5KP32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5KP32-0DC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB is and what it does

The Siemens SENTRON 3VA2110-5KP32-0DC0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current, designed for line protection in distribution panels. Its interrupting capacity hits 187 kA at 240 V and 121 kA at 415/440 V, dropping to 75.6 kA at 500 V and 3.7 kA at 690 V — so at typical 400 V industrial feeds it clears faults up to 121 kA without cascading upstream breakers. The 100 A rating holds flat across the full operating temperature range from -25 °C to 70 °C, meaning no derating is needed for warm enclosures or outdoor cabinets within that band. Power loss at rated current is 12.5 W maximum — manageable for thermal budgeting in a packed panel.

Panel fit and integration

Dimensions are 105 mm wide, 181 mm high, and 86 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without gland-plate modification. The 86 mm depth is the dimension to watch for shallow backboxes or door clearance. It ships with two auxiliary switches (HQ type) and an undervoltage release (UVR) integrated, so the auxiliary contact block and shunt-trip wiring are already accounted for in the panel layout. No separate UVR module to mount alongside. Communication function is built in — the breaker can report status and trip events over the bus, which saves pulling separate signal wires back to the PLC for each MCCB in a motor control center.

Frequently asked questions

What is 3VA2110-5KP32-0DC0's listed depth (86 mm) on this component line?

The depth is 86 mm (3.39 in), which is the critical dimension for shallow enclosures or door clearance.

Will 3VA2110-5KP32-0DC0 drop into a panel that was specified around 3VA1110-5EE32-0LC0 without rewiring?

The 3VA2110-5KP32-0DC0 is a 3-pole, 100 A MCCB with communication and UVR, while the 3VA1110-5EE32-0LC0 is a different frame size and feature set — panel fit and wiring differ. Verify the mounting footprint and auxiliary wiring before substitution.

MPN