The Siemens SENTRON 3VA2110-5KP32-0JH0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient temperature range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel sizing in warm enclosures. Its interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — figures that cover most low-voltage fault scenarios in industrial distribution.
Integration Notes
The shunt trip release allows remote tripping from a PLC or emergency-stop circuit; the auxiliary and alarm switches provide status feedback without additional interface relays.