Skip to main content
Siemens 3VA2110-5MN32-0KL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5MN32-0KL0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5MN32-0KL0

Siemens SENTRON 3VA2110-5MN32-0KL0, molded case circuit breaker, 3-pole, 100 A, breaking capacity 187 kA at 240 V, motor protection design, with phase failure detection and shunt trip.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5MN32-0KL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105MN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2110-5MN32-0KL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classE
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-5MN32-0KL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-5MN32-0KL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5MN32-0KL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2110-5MN32-0KL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5MN32-0KL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB gives you on a motor circuit

The Siemens 3VA2110-5MN32-0KL0 is a 3-pole molded case circuit breaker from the SENTRON family, rated a full 100 A all the way from 40 °C up to 70 °C ambient — no derating headache in a warm panel. It's built for motor protection with phase failure detection built in, so if you lose a leg on a pump or conveyor, this breaker trips and keeps the windings from cooking. Breaking capacity is serious: 187 kA at 240 V, 121 kA at 415 V, and still 75.6 kA at 500 V. That kind of headroom means it'll clear a fault on a big motor starter or a feeder without welding the contacts shut — even on a stiff industrial grid.

Fit and panel integration

The breaker measures 105 mm wide, 181 mm tall, and 86 mm deep — standard SENTRON 3VA footprint. It mounts on a DIN rail or can be screw-fixed to a backplate. The shunt trip (STL) release and the auxiliary switch block (2 aux + 1 trip alarm + 1 electrical alarm) are factory-installed, so no field wiring of add-on kits. Power loss is capped at 10 W max, which keeps the heat out of a tightly packed enclosure. Operating temp range is -25 to 70 °C, storage from -40 to 80 °C — fine for a non-conditioned electrical room or an outdoor panel in most climates.

Frequently asked questions

Where can I buy 3VA2110-5MN32-0KL0 and how do I get a price?

This MCCB is available to order through our distribution network. Submit an RFQ for current pricing and availability — we confirm both at quote time.

What are the key ratings of this MCCB?

Rated 100 A continuous at ambients from 40 to 70 °C, breaking capacity 187 kA at 240 V and 121 kA at 415 V, 3-pole, with phase failure detection and a shunt trip release.

Will 3VA2110-5MN32-0KL0 drop into a panel that was specified around 5SQ2370-2YA05 without rewiring?

The 3VA series is the direct successor to the 5SQ line and shares the same mounting footprint and terminal pattern. It should bolt in without panel modifications, but verify the auxiliary wiring configuration — the 3VA uses a different aux switch block layout.

MPN
3VA2110-5MN32-0KL0