Motor protection breaker with ETU350M trip unit
Protection settings and release
Overload protection (Ir) is adjustable from 40A to 100A, matching the In=100A frame rating. Short-circuit protection (Isd) is set between 3 and 15 times Ir, and the instantaneous pickup (Ii) is fixed at 15 times In. The undervoltage release (UVR) operates on 24V DC — if the control voltage drops, the breaker trips, which is standard practice for emergency-stop or safety-related disconnection circuits.