The Siemens SENTRON 3VA2110-5MN36-0HA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current at 40 °C, with an ETU350M electronic overcurrent release and an integrated shunt trip (STL) release for remote tripping. Rated 100 A at 40 °C through 50 °C, it derates to 90 A at 70 °C — so in a warm enclosure you lose 10 A of headroom; plan your load margin accordingly. Breaking capacity hits 187 kA at 240 V and 121 kA at 415 V, dropping to 17 kA at 690 V — this covers high-fault utility feeds at low voltage but needs coordination study at 690 V. The ETU350M trip unit supports phase failure detection and a voltage trigger, making it suited for motor protection duty where loss-of-phase must trip the breaker.

Siemens 3VA2110-5MN36-0HA0 SENTRON MCCB, 100 A, 3-Pole, Shun
MPN3VA2110-5MN36-0HA0
Siemens SENTRON 3VA2110-5MN36-0HA0, molded case circuit breaker, 3-pole, 100 A, ETU350M electronic trip unit, shunt trip release, breaking capacity 187 kA at 240 V.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Product version | Motor protection |
| Basic switch (supplied) ref. | 3VA2110-5MN36-0AA0 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Current at 40 °C | 100 A |
| Current at 45 °C | 100 A |
| Current at 50 °C | 100 A |
| Current at 55 °C | 96 A |
| Current at 60 °C | 94 A |
| Current at 65 °C | 92 A |
| Current at 70 °C | 90 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 121 kA |
| Breaking capacity at 500 V | 75.6 kA |
| Breaking capacity at 690 V | 17 kA |
| Power loss, max. | 75 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU350M |
| Parameter | Value |
|---|---|
| Main circuit connection type | box terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | Yes |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
Product details
Frequently asked questions
What is the depth of 3VA2110-5MN36-0HA0?
The depth is 86 mm.
What is the width of 3VA2110-5MN36-0HA0?
The width is 105 mm.
MPN
3VA2110-5MN36-0HA0