Skip to main content
Siemens 3VA2110-5MN36-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5MN36-0KA0 SENTRON MCCB, 100 A, 3-Pole, Moto

MPN3VA2110-5MN36-0KA0

Siemens SENTRON 3VA2110-5MN36-0KA0, molded case circuit breaker, 3-pole, 100 A, motor protection version with ETU350M electronic trip unit, shunt trip release, interrupting 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-5MN36-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2110-5MN36-0AA0

Ratings

3VA2110-5MN36-0KA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.75 W

Protection & Trip Unit

3VA2110-5MN36-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M

Construction & Connection

3VA2110-5MN36-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-5MN36-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2110-5MN36-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-5MN36-0KA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

MCCB for motor circuits — what the ratings mean

The Siemens SENTRON 3VA2110-5MN36-0KA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous at 40 °C, built specifically for motor protection duty. The ETU350M electronic trip unit gives you adjustable overload and short-circuit curves plus phase-failure detection — that last one is the difference between catching a lost phase before the motor cooks and finding out when the winding lets go. Interrupting capacity hits 187 kA at 240 V and 121 kA at 415 V, so it clears high-fault bolted shorts without welding its contacts shut. The 800 V rated insulation voltage (Ui) means it's comfortable on 480 V or 600 V class systems with headroom.

Panel fit and integration

Mounts on a DIN rail or panel-mount base. Dimensions are 105 mm wide × 181 mm tall × 86 mm deep — standard 3-pole MCCB footprint for the SENTRON 3VA platform. The shunt trip release (STL) is integrated, so you can remote-trip it from an E-stop or PLC output without adding an external coil module. No auxiliary contacts on this variant, so if you need status feedback to the controller, plan for the separate 3VA9688-0BL33 auxiliary trip block.

Thermal derating and power loss

Rated 100 A up to 50 °C ambient, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. Maximum power dissipation is 75 W — factor that into enclosure heat rise if you're packing several breakers in a sealed panel. Operating range is -25 °C to +70 °C; storage range is -40 °C to +80 °C.

Frequently asked questions

Where can I buy 3VA2110-5MN36-0KA0 and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What is the depth of 3VA2110-5MN36-0KA0?

The depth is 86 mm, with a width of 105 mm and height of 181 mm.

Will 3VA2110-5MN36-0KA0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?

No — the 3VA2110 frame is physically larger (105 mm wide vs the 3VA1010's narrower footprint) and uses a different trip unit. Panel cutouts and bus connections would need modification.

What compliance documentation does Siemens provide for this MCCB?

Standard Siemens SENTRON documentation includes RoHS and REACH declarations; the breaker is designed to meet IEC 60947-2 and UL 489 standards. Specific certificates are available on request.

MPN
3VA2110-5MN36-0KA0