Skip to main content
Siemens 3VA2110-6HL32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-6HL32-0AF0 SENTRON MCCB, 100 A, 242 kA at 24

MPN3VA2110-6HL32-0AF0

Siemens SENTRON 3VA2110-6HL32-0AF0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 242 kA breaking capacity at 240 VAC, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-6HL32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21106HL320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2110-6HL32-0AF0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W
3VA2110-6HL32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2110-6HL32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-6HL32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2110-6HL32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-6HL32-0AF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2110-6HL32-0AF0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current, designed for line protection in distribution panels and industrial switchgear. Its breaking capacity reaches 242 kA at 240 VAC, 187 kA at 415 VAC and 440 VAC, 121 kA at 500 VAC, and 3.7 kA at 690 VAC — figures that give the specifying engineer substantial SCCR headroom for high-fault installations without cascading upstream.

Dimensions are 181 mm high, 105 mm wide, and 86 mm deep — a standard MCCB footprint that fits most DIN-rail or panel-mount enclosures without rework. Power loss is 10 W maximum at rated current, a figure to include in enclosure thermal calculations when grouping multiple breakers.

Ratings & Derating

The 100 A continuous rating holds flat across the full ambient temperature range from 40 °C to 70 °C — no derating required up to the maximum operating temperature of 70 °C. Adjustable thermal-magnetic trip unit covers 150 A to 1 200 A, so the breaker can be tuned to protect downstream conductors or loads within that window. Storage range spans -40 °C to 80 °C; operating range is -25 °C to 70 °C.

Frequently asked questions

Does this breaker include auxiliary contacts?

Yes, it ships with one auxiliary switch and one trip alarm switch (HQ type) pre-installed.

MPN
3VA2110-6HL32-0AF0