It's a 3-pole unit configured for line protection, meaning it guards the feeder, not a specific motor or load downstream. The interrupting capacity is the headline number here: 242 kA at 240 V, 187 kA at 415 V, and still 121 kA at 500 V. This breaker carries a shunt trip release (STL) — the auxiliary release is built in, so you can trip it remotely from a safety circuit or E-stop chain. No undervoltage release, no ground-fault module, no communication function. It's a straightforward line-protection MCCB with a remote-trip option, sized for a panel where you need the interrupting capacity but don't need the extra monitoring layers.

Siemens 3VA2110-6HL32-0HA0 SENTRON MCCB, 100 A, 242 kA at 24
Siemens SENTRON 3VA2 series, molded case circuit breaker (MCCB), 3VA2110-6HL32-0HA0, 100 A rated, 3-pole, line protection, with shunt trip release.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA21106HL320AA0 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 100 A |
| Current at 45 °C | 100 A |
| Current at 50 °C | 100 A |
| Current at 55 °C | 100 A |
| Current at 60 °C | 100 A |
| Current at 65 °C | 100 A |
| Current at 70 °C | 100 A |
| Switching capacity class | H |
| Breaking capacity at 240 V | 242 kA |
| Breaking capacity at 415 V | 187 kA |
| Breaking capacity at 440 V | 187 kA |
| Breaking capacity at 500 V | 121 kA |
| Breaking capacity at 690 V | 3.7 kA |
| Power loss, max. | 10 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU320 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | on both sides nut keeper kit |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | Yes |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 25 000 |
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
| Height (in) | 7.13 in |
| Width (in) | 4.13 in |
| Depth (in) | 3.39 in |
Product details
Frequently asked questions
Where can I buy 3VA2110-6HL32-0HA0 and how do I get a price?
This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate.
What is 3VA2110-6HL32-0HA0's interrupting capacity at 240 V?
242 kA at 240 V, dropping to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V.
Does the 3VA2110-6HL32-0HA0 include a shunt trip?
Yes, it includes a shunt trip release (STL) for remote tripping. No undervoltage release, ground-fault monitoring, or communication function is fitted.