Siemens 3VA2110-6HL32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-6HL32-0JH0 SENTRON MCCB, 100 A, 242 kA at 24

MPN3VA2110-6HL32-0JH0

Siemens SENTRON 3VA2110-6HL32-0JH0, 3-pole molded case circuit breaker, 100 A continuous, 242 kA interrupting at 240 V, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-6HL32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21106HL320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2110-6HL32-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-6HL32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-6HL32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-6HL32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2110-6HL32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-6HL32-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB delivers for your panel

The Siemens SENTRON 3VA2110-6HL32-0JH0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed as the panel warms up. Its interrupting capacity hits 242 kA at 240 V, which means it can safely clear a massive fault without cascading upstream, a critical factor for high-fault installations like transformer secondaries or large motor control centers. At 690 V the interrupting capacity drops to 3.7 kA, so verify the available fault current at your system voltage before specifying.

Integration and mounting

Dimensions are 105 mm wide, 181 mm tall, and 86 mm deep — a standard footprint for SENTRON 3VA frame sizes. The breaker includes a shunt trip release and two auxiliary switches plus a trip alarm switch, giving you remote trip and status feedback without an add-on module. Power loss is capped at 10 W, so thermal management inside a crowded enclosure stays manageable.

Frequently asked questions

Where can I buy 3VA2110-6HL32-0JH0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the interrupting capacity of 3VA2110-6HL32-0JH0 at 240 V?

At 240 V the interrupting capacity is 242 kA, suitable for high-fault installations.

Does 3VA2110-6HL32-0JH0 include auxiliary switches?

Yes, it comes with two auxiliary switches and one trip alarm switch, plus a shunt trip release for remote tripping.

MPN