Rated insulation voltage is 800 V, and the interrupting capacity reaches 242 kA at 240 V AC, dropping to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. The overcurrent release is an ETU320 electronic trip unit, which provides adjustable long-time, short-time, and instantaneous protection.
The IP40 front protection means it is suited for indoor panel mounting where dust ingress is limited; no washdown rating, so keep it behind a sealed enclosure door in wet environments. Maximum power loss is 10 W, which is modest for a 100 A frame — useful when calculating enclosure thermal rise.