Skip to main content
Siemens 3VA2110-6HN32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-6HN32-0CH0 SENTRON MCCB, 100A, 3-Pole, 242kA

MPN3VA2110-6HN32-0CH0

Siemens SENTRON 3VA2110-6HN32-0CH0, 3-pole molded case circuit breaker, 100 A rated current, 242 kA breaking capacity at 240 V, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-6HN32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21106HN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2110-6HN32-0CH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.12.5 W
3VA2110-6HN32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2110-6HN32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-6HN32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2110-6HN32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-6HN32-0CH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

MCCB for 100 A feeder protection

The Siemens 3VA2110-6HN32-0CH0 is a 3-pole SENTRON molded case circuit breaker rated for 100 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to 70 °C. Its interrupting capacity hits 242 kA at 240 V, 187 kA at 415 V, and still holds 121 kA at 500 V, so it handles high-fault utility feeds or transformer-secondaries where fault current runs high.

Built-in undervoltage release and auxiliary switches

The auxiliary switches give remote status feedback (open/closed/tripped) for a PLC or SCADA input.

The 105 mm width matches the common 3-pole slot in SENTRON distribution boards and most industrial enclosures. No special cutout or adapter needed for a standard panel.

Frequently asked questions

Where can I buy 3VA2110-6HN32-0CH0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 3VA2110-6HN32-0CH0 at different voltages?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V — sufficient for most high-fault industrial feeds.

Does 3VA2110-6HN32-0CH0 include an undervoltage release?

Yes, it comes with a factory-fitted undervoltage release (UVR) as standard, plus two auxiliary switches and one trip alarm switch.

MPN
3VA2110-6HN32-0CH0