Skip to main content
Siemens 3VA2110-6HN32-0DL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-6HN32-0DL0 SENTRON MCCB, 100 A, 3-Pole, 242

MPN3VA2110-6HN32-0DL0

Siemens SENTRON 3VA2110-6HN32-0DL0, molded case circuit breaker, 3-pole, 100 A at 40 °C, 242 kA at 240 V, line protection with undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-6HN32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21106HN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2110-6HN32-0DL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.12.5 W
3VA2110-6HN32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2110-6HN32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-6HN32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2110-6HN32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-6HN32-0DL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

It's a 3-pole unit rated for 100 A continuous at 40 °C, with no derating through 70 °C, so it holds its full ampacity across typical panel ambient temperatures. The interrupting ratings are substantial: 242 kA at 240 V and 187 kA at 415 V, which puts it in the high-fault-current class for industrial switchboards where available short-circuit current is high.

The 100 A continuous rating is flat from 40 °C to 70 °C — no thermal derating curve to calculate, which simplifies panel sizing in warm environments. At 690 V the rating drops to 3.7 kA, so if your system voltage is higher than 500 V, confirm the available fault current stays under that limit. This is common for emergency-stop circuits or machinery that must shut down on power loss. The supplied basic switch carries order code 3VA21106HN320AA0, and the auxiliary switch configuration is 2 auxiliary switches plus 1 trip alarm switch plus 1 electrical alarm switch HQ, giving you status feedback for remote monitoring or PLC inputs.

The MCCB measures 105 mm wide, 181 mm high, and 86 mm deep. Mounting is via the four-bolt pattern typical of SENTRON 3VA frames; no DIN-rail clip on this class of breaker.

Frequently asked questions

What is the interrupting rating of 3VA2110-6HN32-0DL0?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V.

What is the continuous current rating and does it derate with temperature?

Rated 100 A continuous from 40 °C through 70 °C — no derating required across that range.

Where can I buy 3VA2110-6HN32-0DL0?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What auxiliary switches and releases does this breaker include?

It includes an undervoltage release (UVR) and an auxiliary switch configuration of 2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ.

MPN
3VA2110-6HN32-0DL0